HomeMy WebLinkAboutResolution 2007-144 declaring the 2006 International Fire Code with local amendments a public record2007-144*
MARANA RESOLUTION NO. 20ftcl
RELATING TO BUILDING; DECLARING THE 2006 INTERNATIONAL FIRE CODE, WITH
LOCAL AMENDMENTS, TO TOWN CODE TITLE 7, ADOPTED BY MARANA
ORDINANCE NO. 2007.20, AS A PUBLIC RECORD FILED WITH THE TOWN CLERK;
AND DECLARING AN EMERGENCY.
BE IT RESOLVED BY THE MAYOR AND COUNCIL OF THE TOWN OF
MARANA, ARIZONA, as follows:
SECTION 1. The 2006 International Fire Code, with local amendments, a copy of which
is attached to and incorporated in this resolution as Exhibit A and three copies of which are on
file in the office of the Town Clerk, is hereby declared to be a public record and ordered to
remain on file with the Town Clerk.
SECTION 2. Since it is necessary for the preservation of the peace, health and safety of
the Town of Marana that this resolution become immediately effective, an emergency is hereby
declared to exist, and this resolution shall be effective immediately upon its passage and
adoption.
PASSED AND ADOPTED BY THE MAYOR AND COUNCIL OF THE TOWN OF
MARANA, ARIZONA, this 2 I't day of August, 2007.
94ayor Ed Honea
ATTEST:
yn C.Yonson, Town Clerk
PPROVED AS TO FORM:
n Attorney
*This is a scrivenor's error. The document was
Council as No. 2007-138 and has been changed to
the correct numbering sequence.
SM
(00005239.DOC /I
approved by
conform to
CIH 611810 7
Town of Marana Fire Code
2006 1FC Amendments
CHAPTER1
ADMINISTRATION
101.2.1 Appendices. The following appendices are adopted as part of this
Code:
Appendix B Fire-flow requirements for buildings
Appendix C Fire hydrant locations and distribution
Appendix D Fire Apparatus Access Roads
Appendix E Hazard Categories (as reference information)
Appendix F Hazard Ranking
Appendix G Cryogenic Fluids - Weight and volume equivalents (as reference
information)
SECTION 102 - APPLICABILITY
Section 102.3 Change of use or occupancy is REVISED to read:
102.3 Change of use or occupancy. The provisions of the International
Building Code shall apply to all buildings undergoing a change of occupancy.
Section 102.4 Application of building code is REVISED to read:
102.4 Application of building code. The design and construction of new
structures shall comply with the International Building Code. Repairs, alterations
and additions to existing structures shall comply with the International Building
Code.
Section 102.5 Historical buildings is REVISED to read:
102.5 Historical buildings. The construction, alteration, repair, enlargement,
restoration, relocation or movement of existing buildings or structures that are
designated as historic buildings when such buildings or structures do not
constitute a distinct hazard to life or property shall be in accordance with the
provisions of the International Building Code.
102.9 Conflicting provisions. Amend to read as follows:
102.9 Conflicting provisions. Where there is a conflict between a general
requirement and a specific requirement, or between this code and any other
code, ordinance or statute, the more restrictive shall apply.
SECTION 104 - GENERAL AUTHORITY AND RESPONSIBILITIES
Section 104.2 is REVISED by ADDING the following subsection:
Section 104.2.1 Permit Fees. Permit fees shall be in accordance with the Town
of Marana and Northwest Fire District fee schedule.
Section 104.6 Official Records. Is REVISED as follows:
Town of Marana Fire Code
2006 1FC Amendments
The fire code official shall keep official records as required by the approved
State of Arizona records retention schedule.
Section 104.6.3 is REVISED by ADDING the following:
The Building Official shall be notified of any fire in a residential structure and
of any fire caused by an electrical or mechanical system within any structure.
SECTION 105 - PERMITS
105.1.1 Permits required is REVISED as follows:
Permits required. Permits required by this code shall be obtained from the
Fire District. It shall be unlawful for any person, firm or corporation to use a
building(s) or premises or engage in any activities for which the fire code
official requires a permit without first having obtained such permit. Permit
fees, if any, shall be paid prior to issuance of the permit. Issued permits shall
be kept on the premises designated herein at all times and shall be readily
accessible for inspection by the fire code official. For information on required
permits, contact the northwest fire district, fire prevention section at (520)
887-1010.
105-1.2 Types of Permits. Is REVISED as follows:
1. Operational permit. An operational permit is one that is issued as a
Building Permit by the Building Services Departments/Northwest Fire District
as reviewed by the fire code official that allows the applicant to conduct an
operation or a business for which a permit is required by Section 105 and that
the Certificate of Occupancy is conditional upon the operation continuing as
approved. Changes in the operation will require new permit applications and
re-issuance of the Certificate of Occupancy.
2. Construction permit. A construction permit is one that is issued as a
Building Permit by the Building Services Department/Northwest Fire District
as reviewed by the fire code official and building plan reviewers. This permit
allows the applicant to construct, install or modify building systems and
equipment for which a permit is required by this or other regulations.
Section 105.6 Required operational permits is REVISED as follows:
105.6 Required operational permits.
The fire code official is authorized to issue operational permits for the operations
set forth in Sections 105.6.1 through 105.6.47.
105.6.2 Amusement buildings
An operational permit is required to operate a temporary special amusement
building. Temporary special amusement buildings shall be operated for a period
of time not to exceed 45 days. Plans for temporary special amusement buildings
2
Town of Marana Fire Code
2006 1FC Amendments
shall be submitted to the northwest fire district fire prevention section 30 days
before the opening of the building or structure to the public.
105.6.4 Carnivals and fairs.
An operational permit is required to conduct a carnival or fair.
105.6.9 Covered mail buildings. An operational permit is required for:
1. The placement of retail fixtures and displays, concession equipment,
displays of highly combustible goods and similar items in the mall.
2. The display of liquid- or gas-fired equipment in the mall.
3. The use of open-flame or flame-producing equipment in the mall.
105.6.13 Exhibits and trade shows.
An operational permit is required to operate exhibits and trade shows.
105.6.14 Explosives.
An operational permit is required for the manufacture, storage, handling, sale or
use of any quantity of explosive, explosive material, fireworks, or pyrotechnic
special effects within the scope of Chapter 33.
105.6.26 Liquid- or gas-fueled vehicles or equipment in assembly buildings.
An operational permit is required to display, operate or demonstrate liquid- or
gas-fueled vehicles or equipment in assembly buildings.
105.6.30 Open burning.
A permit is required for the kindling or maintaining of an open fire or a fire on any
public street, alley, road, or other public or private ground. Instructions and
stipulations of the permit shall be adhered to.
Exception: Recreational fires.
105.6.36 Pyrotechnic special effects material.
An operational permit is required for use and handling of pyrotechnic special
effects material.
105.6.43 Temporary membrane structures, tents and canopies. An
operational permit is required to operate a temporary membrane structure or a
tent having an area in excess of 400 square feet (37M2), or a canopy in excess of
900 square feet (84M).
Exceptions:
1. Tents used exclusively for recreational camping purposes.
Section 105.7 Required construction permits is REVISED as follows:
105.7 Required construction permits.
The fire code official is authorized to issue construction permits for work as set
forth in Sections 105.7.1 through 105.7.12.
3
Town of Marana Fire Code
2006 1FC Amendments
105.7.1 Automatic fire-extinguishing systems. A construction permit is
required for installation of or modification to an automatic fire-extinguishing
system. Maintenance performed in accordance with this code is not considered a
modification and does not require a permit.
105.7.3 Fire alarm and detection systems and related equipment.
A construction permit is required for installation of or modification to fire alarm
and detection systems and related equipment. Maintenance performed in
accordance with this code is not considered a modification and does not require
a permit.
105.7.4 Fire pumps and related equipment.
A construction permit is required for installation of or modification to fire pumps
and related fuel tanks, jockey pumps, controllers, and generators. Maintenance
performed in accordance with this code is not considered a modification and
does not require a permit.
105.7.11 Standpipe systems.
A construction permit is required for the installation, modification, or removal from
service of a standpipe system. Maintenance performed in accordance with this
code is not considered a modification and does not require a permit.
105.7.12 Temporary membrane structures, tents and canopies. A
construction permit is required to erect a temporary, membrane structure or a tent
having an area in excess of 400 square feet (1 9m ), or a canopy in excess of 900
square feet (37M).
Exceptions:
1. Tents used exclusively for recreational camping purposes.
SECTION 108 - BOARD OF APPEALS
Section 108.1 is REVISED as follows:
108.1 Board of appeals established. In order to hear and decide appeals of
orders, decisions or determinations made by the fire code official relative to the
application and interpretation of this code, the Northwest Fire district hereby
establishes that the district's Board of Directors shall serve as the district's board
of appeals. The fire code official shall be an ex officio member of said board but
shall have no vote on any matter before the board. The board shall adopt rules of
procedure for conducting its business, and shall render all decisions and findings
in writing to the appellant with a duplicate copy to the fire code official. The
Board shall have no authority to waive requirements of this code.
Section 108.1.1 Administrative Review is ADDED to read:
108.1.1 Administrative review. Whenever a violation of this code has been found
and the property owner or representative wishes to challenge the application of
this code by the inspection authority, an administrative review may be requested
based on the claim that the intent of this code or the rules legally adopted
4
Town of Marana Fire Code
2006 1FC Amendments
hereunder have been incorrectly interpreted, the provisions of this code do not
fully apply, or an equivalent method of protection or safety is proposed,
The request for an administrative review shall be filed with the fire code official as
follows:
1 . The applicant shall file a written request for administrative review on or
before Friday of each week, not later than 4:30 p.m.
2. The fire code official will conduct the review within 10 working days of the
receipt of the request.
3. The fire code official may use a hearing committee consisting of such staff
as is deemed appropriate to provide additional insight regarding the
request for review.
4. Adequate information shall be provided by the applicant on the request for
review to fully describe the condition(s) in question.
5. The applicant may, but is not required to, meet with the fire code official to
discuss the review.
6. If the administrative review results in upholding the actions of the
inspection staff, the applicant shall comply with the requirement(s) of the
fire code or file an appeal with the district's board of appeals.
Section 109.3 Violation penalties is REVISED to read:
Section 109.3 Violation penalties. Persons who shall violate a provision of this
code or shall fail to comply with any of the requirements thereof or who shall
erect, install, alter, repair or do work in violation of the approved construction
documents or direction of the fire code official, or of a permit or certificate used
under provisions of this code, shall be guilty of a civil infraction, and upon
conviction thereof, punishable by a fine in accordance with the Town of Marana,
Arizona or Pima County, Arizona fine schedule as applicable for such
violation(s). Each day that a violation continues after due notice has been served
shall be deemed a separate offense.
Section 111 Stop work order
Section I 11.1 Order is REVISED by adding at the end:
The stop work order is limited to work performed under this code. The
building official shall be notified of any stop work order.
Section 111.4 Failure to comply is REVISED to read:
111.4 Failure to comply. Any person who shall continue any work after having
been served with a stop work order, except such work as that person is directed
to perform to remove a violation or unsafe condition, shall be liable to a fine in
accordance with the Town Of Marana, Arizona or Pima County, Arizona fine
schedule as applicable for such violation.
5
Town of Marana Fire Code
2006 1FC Amendments
CHAPTER 2
DEFINITIONS
SECTION 201 - GENERAL
Section 201.3 Terms defined in other codes is REVISED to read:
201.3 Terms defined in other codes. Whenever terms are not defined in this
code and are defined by other applicable codes adopted by the jurisdiction, such
terms shall have the meanings ascribed to them as in those codes.
SECTION 202 - GENERAL DEFINITIONS
The following definitions are ADDED as follows:
Barbecue pit. An enclosure in which approved fuels are burned to make a bed
of hot coals over which food is prepared.
Driveway. A vehicular ingress and egress route that serves no more than two
buildings or structures, not including accessory structures, or no more than five
dwelling units.
The following OCCUPANCY CLASSIFICATIONS are REVISED as follows:
Institutional Group 1.
[B] Institutional Group 1. Institutional Group I occupancy includes, among
others, the use of a building or structure, or a portion thereof, in which people,
cared for or living in a supervised environment and having physical limitations
because of health or age, are harbored for medical treatment or other care or
treatment, or in which people are detained for penal or correctional purposes or
in which the liberty of the occupants is restricted. Institutional occupancies shall
be classified as Group 1-1, 1-2,1-3 or 1-4.
Group 1-1. This occupancy shall include buildings, structures or parts thereof
housing more than 10 persons, on a 24-hour basis, who because of age,
mental disability or other reasons, live in a supervised residential environment
that provides personal care services. The occupants are capable of
responding to an emergency situation without physical assistance from staff.
This group shall include, but not be limited to, the following:
Alcohol and drug centers
Assisted living facilities
Congregate care facilities
Convalescent facilities
Group homes
Half-way houses
Residential board and care facilities
Social rehabilitation facilities
6
Town of Marana Fire Code
2006 1FC Amendments
CHAPTER 3
GENERAL PRECAUTIONS AGAINST FIRE
SECTION 302 - DEFINITIONS
Section 302.1 Definitions. The definition of BONFIRE is hereby DELETED (in its
entirety).
SECTION 307 OPEN BURNING AND RECREATIONAL FIRES
Section 307.2 Permit required is here by REVISED as follows:
307.2 Permit required. A burning permit shall be obtained from the fire code
official in accordance with Section 105.6 prior to kindling a fire for recognized
cultural or range or wildlife management practices or prevention or control of
disease or pests. Application for such approval shall only be presented by the
owner and permits issued to the owner of the land upon which the fire is to be
installed. All burn permits require prior approval of Pima County Department of
Environmental Quality.
Section 308.3.6 Theatrical performers. Is hereby REVISED by ADDING the
following subsections:
Section 308.3.6.1 Audience control. The audience shall be at least 30 feet
(9144 mm) away from the closest projection of an open flame device. Audience
control shall be established by use of a physical barrier which can be easily
moved or removed in the event of an emergency and shall remain in place
throughout the entire performance.
Section 308.3.6.2 Attendant. Performances shall be constantly attended by a
person knowledgeable in the use of a fire extinguisher at the rate of at least 1
attendant for every 4 active performers. Attendants shall remain at the
performance until the fire has been extinguished.
Section 308.3.6.3 Fire extinguishers. Adequate fire extinguishing equipment
including but not limited to buckets of water, water soaked rags, water
extinguishers, or charged hose lines, shall be readily available for use during the
performance. Portable fire extinguishers shall be provided at a minimum of one
20bc extinguisher for every four simultaneous performers.
Section' 308.3.6.4 Clearance from combustibles. A 25-foot (7620 mm)
clearance from all combustibles shall be maintained in all directions.
SECTION 311 - VACANT PREMISES
Section 311.2 is hereby AMENDED as follows:
311.2 Safeguarding vacant premises. Temporarily unoccupied buildings,
structures, premises or portions thereof shall be secured and protected in
7
Town of Marana Fire Code
2006 1FC Amendments
accordance with this section. Contact information shall be conspicuously posted,
either on the building or as agreed to by the fire code official.
Section 311.2.2 Fire protection is hereby AMENDED by DELETING Exceptions 1
and 2 (in their entirety).
SECTION 313 - FUELED EQUIPMENT
Section 313.1 Fueled equipment is REVISED as follows:
313.1 Fueled equipment. Fueled equipment, including but not limited to
motorcycles, mopeds, lawn-care equipment and portable cooking equipment,
shall not be operated or repaired within a building, including living spaces of
Group R occupancies.
Exceptions:
1. Buildings or rooms constructed for such use in accordance with the
International Building Code.
2. When allowed by Section 314.
3. Use of LP-gas powered equipment in accordance with NFPA 58.
SECTION 316 - HEAT-PRODUCING APPLIANCES is hereby ADDED as follows:
SECTION 316 - HEAT PRODUCING APPLIANCES
Section 316.1 General. Heating appliances shall be installed and maintained in
accordance with their listing and the jurisdiction's building, electrical, and
mechanical codes. Clearances from combustible material shall be maintained as
set for the in the building and mechanical codes and the product listing.
Section 316.2 Clothes dryers. Clothes dryers shall be frequently cleaned to
maintain the lint trap, mechanical and heating components free from excessive
accumulations of lint.
8
Town of Marana Fire Code
2006 1FC Amendments
CHAPTER 4
EMERGENCY PLANNING AND PREPAREDNESS
Section 403.1 is REVISED by ADDING the following paragraphs:
When the fire code official has determined that a fire watch is needed, such
personnel shall be qualified as deemed by the Fire Official. Fire watch personnel
shall be subject to the fire code official's orders at all times, and shall not be
permitted to perform any duties other than those prescribed by this section or by
the fire code official.
Section 403.2 Special Amusement Buildings is ADDED as follows:
403.2 SPECIAL AMUSEMENT BUILDINGS
Section 403.2.1 Scope. Special amusement buildings used for a period of time
not exceeding 45 days shall conform to the requirements in section 403.2 in
addition to the provisions set forth in IFC Chapters 1, 2, 4, 9 and 10 and the
International Building Code.
Exception: Amusement buildings or portions thereof which are without walls
or a roof and constructed to prevent the accumulation of smoke in assembly
areas.
Section 403.2.2 Permit required. For permit requirements refer to section
105.6.2 of this code.
Section 403.2.3 General. Where mazes, mirrors or other effects are used to
confound the egress path, exits and exit signs shall be approved by the building
official and where practicable, shall comply with the requirements specified in
Chapter 10 of this code.
Section 403.2.4 Travel distance. No portion of a maze may be further than 50
feet from an obvious, marked exit out of the maze.
Section 403.2.5 Hazards. Open flame and flammable and combustible liquids
are prohibited within such occupancies.
Section 403.2.6 Operating at reduced lighting levels.
Section 403.2.6.1 General. When such facilities operate at reduced lighting
levels they shall adhere to the following provisions:
1 - Guide(s). Guides are required when haunted houses; fun houses and
similar uses operate at reduced lighting levels. The guide(s) shall be
responsible for complying with the following provisions:
9
Town of Marana Fire Code
2006 IFC Amendments
A. When people enter such an occupancy, they shall be organized into a
group not to exceed 20 persons (including the guides), and said group
shall be accompanied by guides who shall be familiar with the facility.
B. The guides shall have an operable flashlight on their person at all
times.
C. The guides shall have direct communication with an attendant located
at the switch controlling the house lights.
2. Lighting attendant. There shall be an attendant who can immediately
turn on the house lights in case of an emergency.
3. Change of elevations. Any change of elevation within a building or
structure operating at reduced lighting level shall be provided with a
minimum of one foot candle illumination at floor level.
Section 403.7 Fire protection. Fire protection for amusement buildings shall be
in accordance with Section 903.2.10.4 of this code.
10
Town of Marana Fire Code
2006? 1FC Amendments
CHAPTER5
FIRE SERVICE FEATURES
SECTION 503 - FIRE APPARATUS ACCESS ROADS
Section 503.1 Where required is AMENDED to read:
503.1 Where required. Fire apparatus access roads shall be provided and
maintained in accordance with Section 503.1.1 through 503.1.3, and Appendix D.
Section 503.2 Specifications is AMENDED to read:
503.2 Specifications. Fire apparatus access roads shall be installed and
arranged in accordance with Section 503.2.1 through 503.2.7, and Appendix D.
Section 503.2.7 Grade is AMENDED to read:
503.2.7 Grade. The grade of the fire apparatus road shall comply with the
provisions of Appendix D of this code.
Section 503.6 Security gates is AMENDED to read:
503.6 Security gates. The installation of security gates across a fire apparatus
access road shall be approved by the fire code official. Where security gates are
installed, they shall have an approved means of emergency operation. The
security gates and the emergency operation shall be maintained operational at all
times. See Appendix D of this code for detailed requirements.
Section 503.7 Maintenance is ADDED to read:
503.7 Maintenance. The person(s) in possession of the premises on and into
which a fire apparatus access roadway is required shall be solely responsible for
the maintenance of such roadways and all required signs. No owner, manager
or other person(s) in charge of premises served by a required fire apparatus
access roadway shall abandon or close the fire apparatus access roadway or
any part thereof without permission of the fire code official.
The person(s) in possession of the premises shall be responsible in ensuring that
fire apparatus access roadways are kept clear and unobstructed at all times.
SECTION 505 - PREMISES IDENTIFICATION
Section 505.1 Address numbers is hereby AMENDED to read:
505.1 Address numbers. New and existing buildings shall have approved
address numbers, building numbers or approved building identification placed in
a position that is plainly legible and visible from the street or road fronting the
property. Address numbers shall be in accordance with Pima County or Town of
Marana address display requirements.
SECTION 506 - KEY BOXES
Section 506.1 is revised by Added the second paragraph to read:
11
Town of Marana Fire Code
2006 1FC Amendments
506.1 All commercial buildings equipped with an automatic fire sprinkler system
or automatic fire alarm system shall have a key box installed in an approved
location. Key boxes shall be of an approved type and be of a size suitable for the
number of keys to be placed inside. If keys are for different locks, they shall be
identified accordingly.
SECTION 508 - FIRE PROTECTION WATER SUPPLIES
Section 508.1 Required water supply is AMENDED to read:
508.1 Required water supply. An approved water supply capable of supplying
the required fire flow for fire protection shall be provided to premises upon which
facilities, building or portions of buildings are hereafter constructed or moved into
or within the jurisdiction.
Where commercial property is subdivided with or without the creation of public or
private streets for the expressed purpose of providing said subdivided parcels for
sale or otherwise permitting separate and/or individual development to occur, an
approved water supply cable of providing the required fire flow for fire protection
shall be provided and extended to serve directly any and all subdivided
properties. The required fire flow shall be in accordance with Appendix B of this
code.
Section 508.3 Fire flow is REVISED to read:
508.3 Fire flow. Fire flow requirements for buildings or portions of buildings and
facilities shall be in accordance with Appendix B of this code.
508.5.1 Exceptions #2 is REVISED to read:
For buildings equipped throughout with an approved automatic sprinkler system
installed in accordance with Section 903.3.11 or 903.3.1.2 the distance
requirement shall be 500 feet. The Fire Department connection shall be no
greater than 200 feet from the hydrant.
508.5.4 Obstructions is REVISED by ADDING a second paragraph to read:
Vehicles shall not be placed, parked, or kept within 15 feet of a fire hydrant.
Section 508.5.7 Reflective pavement markers is ADDED to read:
508.5.7 Reflective pavement markers. All fire hydrants shall be identified by
the installation of approved blue reflective pavement markers placed in
accordance with the requirements of the fire code official and the Town of
Marana.
12
Town of Marana Fire Code
2006 1FC Amendments
CHAPTER 9
FIRE PROTECTION SYSTEMS
SECTION 901 - GENERAL
Section 901.2.2 Plans for fire sprinkler systems. Is hereby ADDED:
Section 901.2.2 Plans for fire sprinkler systems. Complete plans and
hydraulic calculations for fire sprinkler systems installations shall be submitted for
review and approval prior to beginning installation, modification or alteration.
Plans shall be drawn to an indicated scale, on sheets of uniform size and shall
show, as a minimum the data required by NFPA 13-2002 Edition, Chapter 8.
Water supply data for hydraulic calculations shall be based on 90 percent of the
available water supply as determined by flow test information.
Section 901.4 Installation is hereby AMENDED by REPEALING the word
"Required" in the second sentence:
Section 901.4 Installation. Fire protection systems shall be maintained in
accordance with the original installation standards for that system. Systems shall
be extended, altered, or augmented as necessary to maintain and continue
protection whenever the building is altered, remodeled or added to. Alterations
to fire protection systems shall be done in accordance with applicable standards.
Section 901.7 Systems out of service is hereby AMENDED by ADDING a third
paragraph to read as follows:
No required fire sprinkler system or fire alarm system shall be placed out of
service for more than 8 hours in any 24 hour period without authorization by the
fire code official.
This section is further REVISED by REPEALING (in their entirety) Sections 901.7.1
through 901.7.6 and REPLACED with the following:
901.7.1 Notification. The person placing the fire protection system (or portion
thereof) out of service shall notify the fire code official of the time the system is
placed out of service and an estimate of time the system (or portion thereof) will
be out of service. Upon completion of the work on the system, the fire code
official must be notified when the system (or portion thereof) is placed back in
service.
SECTION 903 - AUTOMATIC FIRE SPRINKLER SYSTEMS
Section 903.2.1 Group A is DELETED (in its entirety) and REPLACED as follows:
13
Town of Marana Fire Code
2006 1FC Amendments
903.2.1 Group A. An automatic sprinkler system shall be provided throughout all
Group A occupancies.
Section 903.2.2 Is renamed Group B. Group E is renumbered.
903.2.2 Group B. An automatic sprinkler system shall be provided throughout all
Group B occupancies.
Section 903.2.2 Group E #11. is DELETED (in its entirety), RENUMBERED and
REPLACED
903.2.3 Group E. An automatic sprinkler system shall be provided throughout all
Group E occupancies.
Section 903.2.3 Group F is DELETED (in its entirety), RENUMBERED and
REPLACED as follows:
903.2.4 Group F. An automatic sprinkler system shall be provided throughout all
Group F occupancies.
Section 903.2.4 Group H is RENUMBERED as follows:
903.2.5 Group H. Automatic sprinkler systems shall be provided in high-hazard
occupancies as required in Sections 903.2.5.1 through
903.2.5.3.
903.2.5.1 General. An automatic sprinkler system shall be installed in Group
H occupancies.
903.2.5.2 Group H-5 occupancies. An automatic sprinkler system shall be
installed throughout buildings containing Group H-5 occupancies. The design
of the sprinkler system shall not be less than that required under the
International Building Code for the occupancy hazard classifications in
accordance with Table 903.2.5.2.
Where the design area of the sprinkler system consists of a corridor protected
by one row of sprinklers, the maximum number of sprinklers required to be
calculated is 13.
14
Town of Marana Fire Code
2006 1FC Amendments
TABLE 903.2.45.2
GROUP H-5 SPRINKLER DESIGN CRITERIA
LOCATION OCCUPANCY HAZARD
CLASSIFICATION
Fabrication areEls Ordinary Hazard Group 2
Service corridors Ordinary Hazard Group 2
-Storage Rooms without dispensing Ordinary Hazard Group 2
Storage Rooms with dispensing Extra Hazard Group 2
Corridors Ordinary Hazard Group 2
903.2.45.3 Pyroxylin plastics. An automatic sprinkler system shall be provided
in buildi-n-gs, or portions thereof, where cellulose nitrate film or pyroxylin plastics
are manufactured, stored or handled in quantities exceeding 100 pounds (45 kg).
Section 903.2.5 Group I is RENUMBERED as follows:
903.2.6 Group 1. An automatic sprinkler system shall be provided throughout
buildings with a Group I fire area.
Exception: An automatic sprinkler system installed in accordance with
Section 903.3.1.2 or 903.3.1.3 shall be allowed in Group 1-1 facilities.
Section 903.2.6 Group M is DELETED (in its entirety), RENUMBERED and
REPLACED as follows:
903.2.7 Group M. An automatic sprinkler system shall be provided throughout
all Group M occupancies.
Section 903.2.8 Group R is DELETED (in its entirety), RENUMBERED and
REPLACED as follows:
903.2.8 Group R. An automatic sprinkler system shall be provided throughout all
Group R occupancies in accordance with this section.
903.2.8.1 Group R-1. An automatic sprinkler system shall be provided
throughout all Group R-1 occupancies.
903.2.8.2 Group R-2. An automatic sprinkler system shall be provided
throughout all Group R-2 occupancies.
903.2.8.3 Group R-3. An automatic sprinkler system shall be provided
throughout all Group R-3 occupancies that does not meet the fire flow as
outlined in B105.1. An automatic sprinkler system installed in accordance
with Section 903.3.1.2 or 903.3.1.3 shall be allowed in Group R-3
occupancies.
15
Town of Marana Fire Code
2006 1FC Amendments
903.2.8.4 Group R-4. An automatic sprinkler system shall be provided
throughout all newly constructed Group R-4 occupancies in compliance with
NFPA 13R as directed by Marana Ordinance.
Exception: An automatic sprinkler system installed in accordance with
Section 903.3.1.2 or 903.3.1.3 shall be allowed in Group R-4 occupancies.
Exception: Existing R-4 occupancies shall be retrofitted in compliance
with NFPA 13D with in 24 months.
Section 903.2.8 Group S-1 is DELETED (in its entirety), RENUMBERED and
REPLACED as follows:
903.2.9 Group S. An automatic sprinkler system shall be provided
throughout all Group S occupancies.
Section 903.2.10 All occupancies except Groups R-3 and U is DELETED (in its
entirety) and REPLACED as follows:
903.2.10 All occupancies except Groups R-3 and U. An automatic sprinkler
system shall be installed in the locations set forth in Sections 903.2.10 and
903.2.10.2.
Section 903.3.1.1.1 Exempt locations is REVISED by DELETING Item 4:
903.3.1.1.1 Exempt locations. Automatic sprinklers shall not be required in the
following rooms or areas where such rooms or areas are protected with an
approved automatic fire detection system in accordance with Section 907.2 that
will respond to visible or invisible particles of combustion. Sprinklers shall not be
omitted from any room merely because it is damp, of fire-resistance rated
construction or contains electrical equipment.
1 . Any room where the application of water, or flame and water, constitutes a
serious life or fire hazard.
2. Any room or space where sprinklers are considered undesirable because
of the nature of the contents, when approved by the fire code official.
3. Generator and transformer rooms separated from the remainder of the
building by walls and floor/ceiling or roof/ceiling assemblies having a fire-
resistance rating of not less than 2 hours.
903.3.5.1.2 Residential combination services. A single combination
water supply shall be permitted provided that the domestic demand is
added to the sprinkler demand as required by NFPA 13R.
Section 903.3.8 Installation requirements is ADDED as follows:
903.3.8 Access to fire sprinkler riser room. Fire sprinkler risers and shut off
controls shall be located in an enclosed riser room directly accessible from the
outside of the building
Section 903.4 Sprinkler system monitoring and alarms is added as follows:
8. Underground key or hub valves in roadway boxes provided for use by
the municipality of public utility.
16
Town of Marana Fire Code
2006 1FC Amendments
Section 903.4.1 Signals is REVISED as follows:
Exceptions:
1 . For automatic sprinkler systems protecting one- and two-family
dwellings installed in accordance with NFPA1 3D, the water flow switch
shall be permitted to sound a local alarm only.
2. Backflow prevention device shutoff valves shall be locked in the open
position. The backflow prevention shutoff valves shall be electrically
supervised by a tamper switch installed in accordance with NFPA 72
and separately annunciated.
Section 903.6 Existing Buildings is REVISED by ADDING the following
subsection:
903.6.2 Fire area increase. Any addition to an existing structure, where the
square footage of the new addition is greater than 25% of the total square
footage of the existing structure and the required fire flow for the total fire area
(new & existing) is not equal to the fire flow required by Appendix B of the fire
code, shall require that the entire structure be equipped throughout with an
approved automatic fire extinguishing system.
SECTION 904-ALTERNATE AUTOMATIC FIRE-EXTINGUISHING SYSTEMS
Section 904.11.2 System interconnection is AMENDED to read:
904.11.2 System interconnection. The actuation of the fire suppression system
shall automatically shut down the fuel or electrical power supply to the cooking
equipment and to all electrical receptacles located within the perimeter of the
protected exhaust hood. The fuel and electrical supply reset shall be manual.
17
Town of Marana Fire Code
2006 1FC Amendments
CHAPTER10
MEANS OF EGRESS
SECTION 1008 - DOORS, GATES AND TURNSTILES
Section 1008.1.3.4. Access-controlled egress doors. Item 3 is REVISED as
follows:
1008.1.3.4 Access-controlled egress doors. The entrance doors in a means
of egress in buildings with an occupancy in Group A, B, E, M, R-1 or R-2 and
entrance doors to tenant spaces in occupancies in Groups A, B, E, M, R-1 and
R-2 are permitted to be equipped with an approved entrance and egress access
control system which shall be installed in accordance with all of the following
criteria:
1 - A sensor shall be provided on the egress side arranged to detect an
occupant approaching the doors. The doors shall be arranged to unlock by
a signal from or loss of power to the sensor.
2. Loss of power to that part of the access control system which locks the
doors shall automatically unlock the doors.
3. The doors shall be arranged to unlock from a manual unlocking device
located 40 inches to 48 inches (1016 mm to 1219 mm) vertically above the
floor and within 5 feet (1524 mm) of the secured doors. Ready access
shall be provided to the manual unlocking device and the device shall be
clearly identified by a sign that reads: PUSH TO EXIT. Lettering shall be
at least 1 inch (25mm) in height and shall have a stroke of not less that 1/8
inch (3.2mm), on a contrasting background next to unlocking device.
When operated, the manual unlocking device shall result in direct
interruption of power to the lock, independent of the access control system
electronics, and the doors shall remain unlocked for a minimum of 30
seconds.
4. Activation of the building fire alarm system, if provided, shall automatically
unlock the doors, and the doors shall remain unlocked until the fire alarm
system has been reset.
5. Activation of the building automatic sprinkler or fire detection system, if
provided, shall automatically unlock the doors. The doors shall remain
unlocked until the fire alarm system has been reset.
6. Entrance doors in buildings with an occupancy in Group A, B, E or M shall
not be secured from the egress side during periods that the building is
open to the general public.
Section 1008.1.8.6 Delayed egress locks. Item 5 is REVISED as follows:
1008.1.8.6 Delayed egress locks. Approved, listed, delayed egress locks
shall be permitted to be installed on doors serving any occupancy except
Group A, E and H occupancies in buildings that are equipped throughout with
an automatic sprinkler system in accordance with Section 903.3.1.1 or an
18
Town of Marana Fire Code
2006 1FC Amendments
approved automatic smoke or heat detection system installed in accordance
with Section 907, provided that the doors unlock in accordance with Items 1
through 6 below. A building occupant shall not be required to pass through
more than one door equipped with a delayed egress lock before entering an
exit.
1 . The doors unlock upon actuation of the automatic sprinkler system or
automatic fire detection system.
2. The doors unlock upon loss of power controlling the lock or lock
mechanism.
3. The door locks shall have the capability of being unlocked by a signal from
the fire command center.
4. The initiation of an irreversible process which will release the latch in not
more than 15 seconds when a force of not more than 15 pounds (67 N) is
applied for 1 second to the release device. Initiation of the irreversible
process shall activate an audible signal in the vicinity of the door. Once
the door lock has been released by the application of force to the
releasing device, relocking shall be by manual means only.
Exception: Where approved, a delay of not more than 30 seconds is
permitted.
5. A sign shall be provided on the door located above and within 12 inches
(305 mm) of the release device reading: PUSH UNTIL ALARM SOUNDS.
DOOR CAN BE OPENED IN 15 [30] SECONDS. Lettering shall be at
least 1 inch (25mm) in height and shall have a stroke of not less than 1/8
inch (3.2mm), on a contrasting background.
6. Emergency lighting shall be provided at the door.
19
Town of Marana Fire Code
2006 1FC Amendments
CHAPTER11
AVIATION FACILITIES
SECTION 1106 - AIRCRAFT FUELING
Section 1106.3 Construction of aircraft-fueling vehicles and accessories is
REVISED by ADDING the words "and NFPA 385" to the end of the sentence as
follows:
1106.3 Construction of aircraft-fueling vehicles and accessories.
Aircraft-fueling vehicles shall comply with this section and shall be designed and
constructed in accordance with NFPA 407 and NFPA 385.
CHAPTER14
FIRE SAFETY DURING CONSTRUCTION AND DEMOLITION
SECTION 1410 - ACCESS FOR FIRE FIGHTING
Section 1410.2 Key boxes is REVISED as follows:
1410.2 Key boxes or padlocks. Key boxes or padlocks shall be provided as
required by Chapter 5.
SECTION 1412 - WATER SUPPLY FOR FIRE PROTECTION
Section 1412.1 When required is REVISED as follows:
1412.1 When required. Fire hydrants connected to an approved water supply
for fire protection, shall be installed and in service prior to placing combustible
material on site.
SECTION 1414 - AUTOMATIC SPRINKLER SYSTEMS
Section 1414.1 Completion before occupancy is REVISED as follows:
1414.1 Completion before occupancy. In buildings where an automatic
sprinkler system is required by this code or the International Building Code, it
shall be unlawful to occupy any portion of a building or structure until the
automatic sprinkler system installation has been tested and approved, except as
provided in Section 105.3.4.
20
Town of Marana Fire Code
2006 1FC Amendments
CHAPTER 22
SERVICE STATIONS AND REPAIR GARAGES
SECTION 2208 - COMPRESSED NATURAL GAS MOTOR FUEL-DISPENSING
FACILITIES
Section 2208.3. Location of dispensing operation and equipment is REVISED
by ADDING the subsection as follows:
2208.3 Location of dispensing operations and equipment. Compression,
storage and dispensing equipment shall be located above ground, outside.
Exceptions:
1 . Compression, storage or dispensing equipment shall be allowed in
buildings of noncombustible construction, as set forth in the
International Building Code, which are unenclosed for three quarters or
more of the perimeter.
2. Compression, storage and dispensing equipment shall be allowed
indoors in accordance with Chapter 30.
2208.3.1 Location on property. In addition to the requirements of Section
2203.1, compression, storage and dispensing equipment shall be installed as
follows:
1. Not beneath power lines.
2. Ten feet (3048 mm) or more from the nearest building or lot line which
could be built on, public street, sidewalk, or source of ignition.
Exception: Dispensing equipment need not be separated from canopies
that are constructed in accordance with the International Building Code
and which provide weather protection for the dispensing equipment.
3. Twenty-five feet (7620 mm) or more from the nearest rail of any railroad
track and 50 feet (15 240 mm) or more from the nearest rail of any railroad
main track or any railroad or transit line where power for train propulsion is
provided by an outside electrical source such as third rail or overhead
catenary.
4. Fifty feet (15 240 mm) or more from the vertical plane below the nearest
overhead wire of a trolley bus line.
2208.3.2 Vehicle impact protection. Vehicle impact protection for CNG gas
storage containers, pumps and dispensers shall be provided in accordance with
Section 312.
21
Town of Marana Fire Code
2006 1FC Amendments
CHAPTER 24
TENTS, CANOPIES AND OTHER MEMBRANE
STRUCTURES
SECTION 2403 - TEMPORARY, TENTS, CANOPIES AND MEMBRANE
STRUCTURES
2403.2 Approval required. Tents and membrane structures having an area in
excess of 400 square feet (37M2 ) and canopies in excess of 900 square feet
(84M2) shall not be erected, operated or maintained for any purpose,without first
obtaining a permit and approval from the fire code official.
Exceptions:
1. Tents used exclusively for recreational camping purposes.
Section 2403.8.2 Location is REVISED as follows:
2403.8.2 Location. Tents, canopies or membrane structures shall not be
located within 20 feet (6096 mm) of lot lines, buildings, other tents, canopies or
membrane structures. For the purpose of determining required distances,
support ropes and guy wires shall be considered as part of the temporary
membrane structure, tent or canopy.
Exceptions:
1. Separation distance between membrane structures, tents and
canopies not used for cooking, is not required when the aggregate
floor area does not exceed 15,000 square feet (1394 m2).
2. Membrane structures, tents or canopies need not be separated from
buildings when all of the following conditions are met:
2.1. The aggregate floor area of the membrane structure, tent or
canopy shall not exceed 10,000 square feet (929 m2).
2.2. The aggregate floor area of the building and membrane
structure, tent or canopy shall not exceed the allowable floor
area including increases as indicated in the International
Building Code.
2.3. Required means of egress provisions are provided for both the
building and the membrane structure, tent or canopy, including
travel distances.
2.4. Fire apparatus access roads are provided in accordance with
Section 503.
Section 2403.12.3 Exit openings from tents. Item 2 is REVISED as follows:
2403.12.3 Exit openings from tents. Exit openings from tents shall remain
open unless covered by a flame-resistant curtain. The curtain shall comply with
the following requirements:
22
Town of Marana Fire Code
2006 1FC Amendments
1 - Curtains shall be free sliding on a metal support. The support shall be a
minimum of 80 inches (2032 mm) above the floor level at the exit. The
curtains shall be so arranged that, when open, no part of the curtain
obstructs the exit.
2. Curtains shall be of a color, or colors, that contrasts with the color of the
tent or is adequately marked otherwise indicating an exit opening.
Section 2403.12.4 Doors is hereby REVISED as follows:
2403.12.4 Doors. Exit doors shall swing in the direction of exit travel. To avoid
hazardous air and pressure loss in air-supported membrane structures, such
doors shall be automatic closing against operating pressures. Opening force at
the door edge shall not exceed 15 pounds (7 kg). Doors that latch shall have
panic hardware installed and operating at all times.
CHAPTER 26
WELDING AND OTHER HOT WORK
SECTION 2604 - FIRE SAFETY REQUIREMENTS for Welding and Hot work
Section 2604.2.6 Fire extinguisher is REVISED as follows:
2604.2.6 Fire extinguisher. A minimum of one portable fire extinguisher
complying with Section 906 and with a minimum 2-A:20-B:C rating shall be
readily accessible within 30 feet (9144 mm) of the location where hot work is
performed. The fire extinguisher(s) shall be readily accessible without
climbing stairs or ladders.
Section 2604.3.1 Pre-hot-work check is REVISED as follows:
2604.3.1 Pre-hot-work check. A pre-hot-work check shall be conducted prior to
work to ensure that all equipment is safe and hazards are recognized and
protected. A report of the check shall be kept at the work site during the work and
available upon request. The pre-hot-work check shall determine all of the
following:
1 . Hot work equipment to be used shall be in satisfactory operating condition
and in good repair. Damaged, leaking or worn hoses shall not be used.
2. Hot work site is clear of combustibles or combustibles are protected.
3. Exposed construction is of noncombustible materials or, if combustible,
then protected.
4. Openings are protected.
5. Floors are kept clean.
6. No exposed combustibles are located on the opposite side of partitions,
walls, ceilings or floors.
7. Fire watches, where required, are assigned.
23
Town of Marana Fire Code
2006 1FC Amendments
8. Approved actions have been taken to prevent accidental activation of
suppression and detection equipment in accordance with Sections
2604.1.8 and 2604.1.9.
9. Fire extinguishers and fire hoses (where provided) are operable and
available.
SECTION 2606 - ELECTRIC ARC HOT WORK
Section 2606.4 Emergency disconnect is REVISED as follows:
2606.4 Emergency disconnect. A switch or circuit breaker shall be provided so
that fixed electric welders and control equipment can be disconnected from the
supply circuit. The disconnect shall be installed in accordance with the ICC
Electrical Code. The disconnect shall be marked EMERGENCY DISCONNECT
and shall be visible from the equipment.
CHAPTER 33
EXPLOSIVES AND FIREWORKS
SECTION 3308 - FIREWORKS DISPLAY
Section 3308.10 Disposal is REVISED as follows:
3308.10 Disposal. Any unexploded shells or live components found after the
display shall not be approached or handled until at least (1) hour has elapsed from
the time the shells were fired. Any unexploded aerial shells or live components
become the responsibility of the fire official and the operator. Shells that fail to lift
from the mortar shall be considered misfires and shall be evaluated by the operator
prior to any action taken. Shells that explode inside the mortar shall be evaluated by
the fire code official and the operator prior to any action taken.
CHAPTER 34
FLAMMABLE AND COMBUSTIBLE LIQUIDS
SECTION 3404 - STORAGE
Section 3404.3.3.3 Clear means of egress is REVISED as follows
3404.3.3.3 Clear means of egress. Storage of any liquids, including stock for
sale, shall not be stored within 10 feet of an exit door or be allowed to obstruct
physically the route of egress.
SECTION 3406 - SPECIAL OPERATIONS
Section 3406.5.4.5 Commercial, industrial, government or manufacturing is
REPLACED the first paragraph with the following:
24
Town of Marana Fire Code
2006 1FC Amendments
3406.5.4.5 Commercial, industrial, governmental or manufacturing. The
transferring of liquids used as fuels from tank vehicles into the fuel tanks of motor
vehicles or special equipment located at commercial, industrial, governmental or
manufacturing establishments is allowed where permitted, provided such
dispensing operations are conducted in accordance with this section.
Section 3406.5.4.5 Commercial, industrial, government or manufacturing is
further REVISED by ADDING the following subsections:
25. Prior to removal of the fuel cap, the bond wire cable shall be securely
clamped to the vehicle being fueled.
26.At no time shall the fueling hose extend across a trafficable lane
without florescent traffic cones conspicuously placed so that all
vehicle traffic is blocked. Vehicles shall not drive over any delivery
hose.
27. Fuel expansion space shall be provided in each motor vehicle tank to
prevent overflow.
28.The fuel cap of the vehicle being fueled shall be replaced prior to
disconnecting the bonding cable.
Section 3406.5.4.6 Prohibition is ADDED to read:
3406.5.4.6 Prohibition. Tank vehicles and tank trailers shall not be used as on-
site storage containers.
CHAPTER 38
LIQUEFIED PETROLEUM GASES
SECTION 3803 - INSTALLATION OF EQUIPMENT
Section 3803.2.1.7 Use for food preparation is DELETED (in its entirety) and
REPLACED with the following:
3803.2.1.7 USE FOR FOOD PREPARATION. Listed and approved LP-gas
commercial food service appliances shall be permitted to be used inside
restaurants and in attended commercial food catering operations provided that
no commercial food service appliances shall have more than two, 1 0-oz non-
refillable butane gas containers having a maximum water capacity of 1.08 lbs.
per container connected directly to the appliance at any time and containers shall
not be manifolded. The appliance fuel container(s) shall be an integral part of the
listed, approved commercial food service device eind shall be connected without
the use of a rubber hose. Butane containers shall be listed. Storage in
25
Town of Marana Fire Code
2006 1FC Amendments
restaurants and at food service locations of 1 0-oz butane non-refillable
containers shall be limited to no more than twenty-four containers.
SECTION 3811 PARKING AND GARAGING
Section 3811.2.2 Durations exceeding I hour is REVISED by DELETING item #1.
3811.2.2 Durations exceeding I hour. Liquefied petroleum gas tank vehicles
parked at any one point for longer thanl hour shall be located as follows:
1 . Inside of a bulk plant.
2. At other approved locations not less than 50 feet (15240 mm) from
buildings other than those approved for the storage or servicing of such
vehicles.
26
Town of Marana Fire Code
2006 IFC Amendments
APPENDIX A
BOARD OF APPEALS
The provisions contained in this appendix are not mandatory unless
specifically referenced in the adopting ordinance.
Appendix A is REVISED as follows:
SECTION A101 GENERAL
A101.1 Scope. A Northwest Fire District - board of appeals is hereby
established for the purpose of hearing applications for modification of the
requirements of the Northwest Fire District Fire Code pursuant to the
provisions of Section 108. The board shall be established and operated in
accordance with this section, and shall be authorized to hear evidence from
appellants and the fire code official pertaining to the application and intent of
this code for the purpose of issuing orders pursuant to these provisions.
A101.2 Membership. The membership of the board shall consist of all of the
voting members of the Northwest Fire District Board of Directors.
A101.3 Terms of office. Members shall be appointed for terms in
accordance with district by-laws.
A101.3.1 Initial appointments. Appointments to the board shall be in
accordance with district by-laws.
A101.3.2 Vacancies. Vacancies shall be filled in accordance with district
by-laws.
A101.3.3 Removal from office. Members shall be removed from office
filled in accordance with district by-laws.
A101.4 Quorum. A majority of the board members shall constitute a quorum.
In varying the application of any provisions of this code or in modifying an
order of the fire code official, affirmative votes of the majority present shall be
required.
Al 01.5 Secretary of board. The District shall provide a secretary to the
board, who shall keep a detailed record of all its proceedings, which shall set
forth the reasons for its decisions, the vote of each member, the absence of a
member and any failure of a member to vote.
A101.6 Legal counsel. The jurisdiction shall furnish legal counsel to the
board to provide members with general legal advice concerning matters
before them for consideration. Members shall be represented by legal
27
Town of Marana Fire Code
2006 1FC Amendments
counsel at the jurisdiction's expense in all matters arising from service within
the scope of their duties.
A101.7 Meetings. The board shall meet at least once a month. In any
event, the board shall meet within 10 days after notice of appeal has been
received.
A101.8 Conflict of interest. Members with a material or financial interest in
a matter before the board shall declare such interest and refrain from
participating in discussions, deliberations, and voting on such matters.
A11011.9 Decisions. Every decision shall be promptly filed in writing in the
office of the fire code official and shall be open to public inspection. A certified
copy shall be sent by mail or otherwise to the appellant, and a copy shall be
kept publicly posted in the office of the fire code official for 2 weeks after filing.
A101.10 Procedures. The board shall be operated in accordance with the
district's by-laws.
28
Town of Marana Fire Code
2006 IFC Amendments
APPENDIX B
FIRE-FLOW REQUIREMENTS FOR BUILDINGS
Section B105.2 Buildings other than one- and two-family dwellings is REVISED
as follows:
13105.2 Buildings other than one- and two-family dwellings. The minimum
fire flow and flow duration for buildings other than one- and two-family dwellings
shall be as specified in Table 13105.11.
Exception: A reduction in required fire flow of up to 75 percent, as approved,
is allowed when the building is provided with an approved automatic sprinkler
system installed in accordance with Section 903.3.1.1 or 903.3.1.2 of the
International Fire Code. The resulting fire flow shall not be less than 1,500
gallons per minute (5678 I/min) for the prescribed duration as specified in
Table B105.1.
29
Town of Marana Fire Code
2006 IFC Amendments
APPENDIX D FIRE APPARATUS ACCESS ROADS is REVISED and RENUMBERED as
follows:
APPENDIX D
FIRE APPARATUS ACCESS ROADS
SECTION D101 - GENERAL
D101.1 Scope. Fire apparatus access roads shall be in accordance with this
appendix and all other applicable requirements of the intemational fire code.
SECTION D102 - REQUIRED ACCESS
D102.1 Access and loading. Facilities, buildings or portions of buildings
hereafter constructed shall be accessible to fire department apparatus by way of
an approved all-weather - fire apparatus access road with an asphalt, concrete or
other approved driving surface capable of supporting the imposed load of fire
apparatus weighing at least 75,000 pounds (34 050 kg).
SECTION D103 MINIMUM SPECIFICATIONS
D103.1 Access road width with a hydrant. Where a fire hydrant is located on
a fire apparatus access road, the minimum road width shall be 26 feet (7925
mm). See Figure D103.1
D103.2 Grade. Fire apparatus access roads shall not exceed 12 percent in
grade.
Exception: Grades steeper than 10 percent as approved by the fire code
official.
D103.3 Driveways. Driveways exceeding 150 feet in length providing access to
dwellings units shall provide a minimum unobstructed width of 14 feet (3658 mm)
and a minimum unobstructed height of 13 feet 6 inches (4115 mm). Driveways in
excess of 150 feet (45 720 mm) in length shall be provided with turnarounds.
Driveways in excess of 200 feet (60 960 mm) in length and less than 20 feet
(6096 mm) in width shall be provided with turnouts in addition to turnarounds.
A driveway shall not serve in excess of five dwelling units.
Driveway turnarounds shall have inside turning radii of not less than 30 feet
(9144 mm) and outside turning radii of not less than 45 feet (13 716 mm).
Driveways that connect with a road or roads at more than one point may be
considered as having a turnaround if all changes of direction meet the radii
requirements for driveway turnarounds.
30
Town of Marana Fire Code
2006 1FC Amendments
Driveway turnouts shall be an all-weather road surface at least 10 feet (3048
mm) wide and 30 feet (9144 mm) long. Driveway turnouts shall be located as
required by the code official.
Vehicle load limits shall be posted at both entrances to bridges on driveways and
private roads. Design loads for bridges shall be established by the code official.
D103.4 Turning Radius. The minimum turning radius shall be based on a SU-
30 design vehicle.
D103.5 Dead ends. Dead-end fire apparatus access roads in excess of 150 feet
(45,720 mm) shall be provided with width and turnaround provisions in
accordance with Table D1 03.5.
TABLE D103.5
REQUIREMENTS FOR DEAD-END FIRE APPARATUS ACCESS ROADS
LENGTH WIDTH
j
(FEET) (FEET) TURNAROUNDS REQUIRED
0-150 20 NONE REQUIRED
151-600 20 HAMMERHEAD, "Y" OR CUL-DE-SAC IN ACCORDANCE
WITH FIGURES D1 03.1, D1 03.2 AT TERMINAL END
HAMMERHEAD, "Y" OR CUL-DE-SAC IN ACCORDANCE
601-1200 26 WITH FIGURES D103.1, D103.2 AT TERMINAL END AND
MIDWAY
APPROVED AUTOMATIC SPRINKLER SYSTEM INSTALLED
OVER 1200 26 THROUGHOUT ALL OCCUPANCIES. HAMMERHEAD, "Y" OR
CUL-DE-SAC IN ACCORDANCE WITH FIGURES D103.1,
D103.2 AT TERMINAL END AND AT EACH 600 FEET.
D103.6 Fire apparatus access road gates. Gates securing the fire
apparatus access roads shall comply with all of the following criteria:
1 . The minimum gate width shall be 20 feet (6096 mm) when serving two
directions, or 14 feet when serving a single direction.
2. Gates shall be of the swinging or sliding type.
3. Construction of gates shall be of materials that allow manual operation
by one person.
4. Gate components shall be maintained in an operative condition at all
times and replaced or repaired when defective.
5. Electric gates shall be equipped with and have installed, approved
preemptive control opening equipment compatible with the fire
department's existing system. A key switch will also be required on all
electric control gates.
31
Town of Marana Fire Code
.2006 1FC Amendments
6. Manual opening gates shall not be locked with a padlock or chain and
padlock unless they are capable of being opened by means of forcible
entry tools or a key box containing the key(s) to the lock is installed at
the gate location.
7. Locking device specifications shall be submitted for approval by the fire
code official.
D103.6.1 Existing Fire Apparatus Access Road Gates.- Existing
gates securing fire apparatus access roads shall comply with d 103.6.
Exception: existing electric gates shall have installed approved
preemptive control opening equipment compatible with the fire
department's existing system within 18 months from the effective
date of this code.
D103.7Signs. Where required by the fire code official, fire apparatus access
roads shall be marked with permanent NO PARKING-FIRE LANE signs
complying with District and Town of Marana standards. Signs shall have a
minimum dimension of 12 inches (305 mm) wide by 18 inches (457 mm) high
and have red letters on a white reflective background. Signs shall be posted
on one or both sides of the fire apparatus road as required by Section D1 03.7
. 1 or D1 03.7.2. Compliance with the provisions of this section shall be at no
expense to the District or the Town.
D1 03.7.1 Roads 20 feet wide, but less than - 26 feet in width. Fire
apparatus access roads less than 26 feet wide (6096 to 7925 mm)
shall be posted on both sides as a fire lane.
D1 03.6 7. 2 Roads 26 feet wide, but less than 32 in width. Fire
apparatus access roads 26 feet wide (7925 mm) but less than 32 feet
wide (9754 mm) shall be posted on one side of the road as a fire lane.
Where parking lanes are provided, they must be 8 feet in width. This is
measured from the back of a wedge or rolled curb or the face of a
vertical curb.
Section D106 - MULTI-FAMILY RESIDENTIAL DEVELOPMENTS
D106.1 Projects having more than 100 dwelling units.
ADD the following:
and shall meet the requirements of D1 04.3.
D106.2 Projects having more than 200 dwelling units
ADD the following:
and shall meet the requirements of D104.3.
32
Town of Marana Fire Code
2006 1FC Amendments
The following have been deleted and reserved from these amendments
105.6.5 Cellulose nitrate film. DELETED/RESERVED
105.6.3 Aviation facilities. DELETED/RESERVED
105.6.1 Aerosol products. DELETED/RESERVED
105.6.6. Combustible dust-producing operations. DELETED/RESERVED
105.6.7 Combustible fibers. DELETED RESERVED
105.6.8. Compressed gases. DELETED/RESERVED
105.6.10 Cryogenic fluids. DELETED/RESERVED
105.6.11 Cutting and welding. DELETED/RESERVED
105.6.12 Dry cleaning plants. DELETED/RESERVED
105.6.15 Fire hydrants and valves. DELETED/RESERVED
105.6.16 Flammable and combustible liquids. DELETED/RESERVED
105.6.17 Floor finishing. DELETED/RESERVED
105.6.18 Fruit and crop ripening. DELETED/RESERVED
105.6.19 Fumigation and thermal insecticidal fogging. DELETED/RESERVED
105.6.20 Hazardous materials. DELETED/RESERVED
105.6.21 HPM facilities. DELETED/RESERVED
105.6.22 High-piled storage. DELETE D/RES ERVED
105.6.23 Hot work operations. DELETED/RESERVED
105.6.24 Industrial ovens. DELETE D/RES ERVED
105.6.25 Lumber yards and woodworking plants. DELETED/RESERVED
105.6.27 LP-gas. DELETED/RESERVED
105.6.28 Magnesium. DELETED/RESERVED
105.6.29 Miscellaneous combustible storage. DELETE D/RES E RVED
105.6.31 Open flames and torches. DELETED/RESERVED
105.6.32 Open flames and candles.
105.6.33 Organic coatings. DELETED RESERVED
105.6.34 Places of assembly.
105.6.35 Private fire hydrants. DELETED/RESERVED
105.6.37 Pyroxylin plastics. DELETED/RESERVED
105.6.38 Refrigeration equipment. DELETED/RESERVED
105.6.39 Repair garages and motor fuel-dispensing facilities. DELETED/
RESERVED
105.6.40 Rooftop heliports. DELETE D/RES ERVE D
105.6.41 Spraying or dipping. DELETED/RESERVED
105.6.42 Storage of scrap tires and tire byproducts. DELETED/RESERVED
105.6.44 Tire-rebuilding plants. DELETED/RRESERVED
105.6.45 Waste handling. DELETED/RESERVED
105.6.46 Wood products. DELETED/RESERVED
105.7.3 Compressed gases. DELETE D/RESE RVE D
105.7.6 Flammable and combustible liquids. DELETED/RESERVED
105.7.7 Hazardous materials. DELETED/RESERVED
105.7.8 Industrial ovens. DELETED/RESERVED
105.7.9 LP-gas. DELETED/RESERVED
105.7.10 Private fire hydrants. DELETED/RESERVED
33
Town of Marana Fire Code
2006 lFC Amendments
105.7.11 Spraying or dipping. DELETED/RESERVED
302.1 Definitions. The definition of BONFIRE is hereby DELETED/RESERVED.
307.3.1 Bonfires is hereby REPEALED (in its entirety) and the Section is
RESERVED.
34